Analysis of thermal stresses in horizontal delivery water heaters
- Authors: Bilan A.V.1, Plotnikov P.N.2
-
Affiliations:
- Ural Turbine Works
- Ural Federal University
- Issue: Vol 63, No 11 (2016)
- Pages: 781-786
- Section: Steam-Turbine, Gas-Turbine, and Combined-Cycle Plants and Their Auxiliary Equipment
- URL: https://bakhtiniada.ru/0040-6015/article/view/172432
- DOI: https://doi.org/10.1134/S004060151611001X
- ID: 172432
Cite item
Abstract
Analysis of thermal stresses in tubes and a compensator, taking into account water heating in each heater bunch and temperature at which its mounting is implemented, and of stresses on pressure is presented. The 3D-model of the horizontal delivery water heater of PSG-4900-0.3-1.14 type is used. The tube plate is represented as the 3D-body with 6863 holes with offset center of the perforated area, the steam space shell is represented as a cylindrical casing, the bottoms of water chambers are considered as elliptical casings, the four-lens compensator is represented in the form of toroidal casings, and the tubes are considered as beams operating in tensile-compression and bending in two planes. Calculations were carried out for different temperatures of superheated steam and a steam space shell, respectively, as well as designs with compensator and without it. Various temperature values of the tubes on the passes were calculated and set. The studies were carried out taking into account nonaxis-symmetrical spacing the tube plate and compensator deformation. The calculation results of tensile-compression stresses in the tubes are presented. Furthermore, the central tubes experience compressive stresses, whose maximal values take place on the border between the tubes of the fourth and of the first passes. For its decrease, it is recommended to increase the distance between the tubes of these passes. The tension stresses in the peripheral tubes are the maximal stresses. To reduce the stresses and, therefore, increase service life of the delivery water heater at using wet or superheated (not more than by 30–50°C) steam in it (the larger value refers to the brass tubes and the water pressure of 1.6–2.5 MPa), it is necessary to recommend the noncompensatory design at using the steam superheated by more than 30–50°C (at Ural Turbine Works, it is the turbines of T-250/300-23.5 and T-113/145-12.4 types with intermediate superheating) and to recommend the installation of the compensator operating only at compression.
About the authors
A. V. Bilan
Ural Turbine Works
Author for correspondence.
Email: Andrey820325@mail.ru
Russian Federation, ul. Frontovykh Brigad 18, Yekaterinburg, 620017
P. N. Plotnikov
Ural Federal University
Email: Andrey820325@mail.ru
Russian Federation, ul. Sof’i Kovalevskoi 5, Yekaterinburg, 620002
Supplementary files